16A C Curve B-HP RCBO Heat Pump Consumer Unit
16A C Curve B-HP RCBO Heat Pump Consumer Unit from WCED Whitecliffe, model WME06/HP16C, provides dedicated protection for the heat pump supply and two separately protected auxiliary circuits. The 6-module board includes a Type 2 surge protection device and a main switch isolator.
Meets Vaillant’s High-Frequency Protection Requirements
The dedicated 16A C Curve Type B-HP RCBO meets Vaillant’s published residual-current protection requirements: Type B protection rated to at least 20 kHz, with a minimum tripping threshold of 150 mA at frequencies above 1 kHz. The RCBO’s 30 mA rated residual operating current and the 150 mA high-frequency threshold describe its response under different conditions.
Choose the WME06/HP16C where the exact Vaillant heat pump model and circuit design call for 16A C Curve overcurrent protection. The 16A rating and C Curve apply to overcurrent protection, while Type B-HP describes the residual-current protection. See the Vaillant aroTHERM plus installer’s quick guide.
Why Some Inverter-Driven Heat Pumps Need Type B-HP
An inverter varies compressor speed by switching electronically. The inverter and its filters can produce high-frequency earth leakage during normal operation, while certain faults can produce smooth DC residual current. Type B protection detects smooth DC residual fault currents. Where the heat pump manufacturer also specifies a high-frequency response, the protective device must meet the stated frequency range and trip thresholds. That response helps reduce unwanted trips caused by normal inverter leakage.
When Is Standard Type B Suitable?
A standard Type B RCD or RCBO can be suitable for other heat pumps where the manufacturer permits it and the device meets the requirements for that model. If the instructions specify a frequency range or tripping threshold, compare those figures with the protective device’s datasheet.
What’s Included in the WCED WME06/HP16C?
- 1 x WCED WME06 6-module consumer unit enclosure
- 1 x 16A C Curve Type B-HP RCBO for the heat pump circuit
- 2 x 16A B Curve Type A RCBOs for auxiliary circuits
- 1 x Type 2 surge protection device (SPD)
- 1 x main switch isolator
The two auxiliary RCBOs can protect separate loads such as controls or an immersion heater where the load and circuit design suit their ratings. The Type 2 SPD helps protect connected equipment against transient overvoltages.
Dedicated Heat Pump RCBO Specifications
- Rated current and overcurrent trip curve: 16A, C Curve
- Residual-current protection: Type B-HP
- Rated residual operating current: 30 mA
- Rated breaking capacity: 10 kA
- Pole configuration: 1P+N with switched live and neutral
- Operation: Bi-directional
- Mounting: 18 mm single module on 35 mm DIN rail
Related Heat Pump Circuit Protection
Browse our heat pump consumer units for other board configurations or view our individual heat pump RCBOs.