GARO DTPN48 15 Way 3 Phase Distribution Board
The GARO DTPN48 15 Way 3 Phase Distribution Board supports compatible outgoing MCBs, RCBOs and AFDDs, allowing electricians to configure circuit protection according to the installation requirements. The factory-fitted protective MCB is dedicated to the Type 2 SPD and cannot be used for an additional outgoing circuit.
Key Features – GARO DTPN48 15 Way 3 Phase Distribution Board
- Usable three-phase capacity: 15 outgoing ways after allowing for the SPD protective MCB.
- Nominal capacity: 16 three-phase ways / 48 single-phase ways.
- Single-phase module equivalents: 45 remaining positions, depending on the widths of outgoing devices.
- Surge protection: factory-fitted Type 2 SPD with dedicated protective MCB.
- Main switch: 125A four-pole switch fitted as standard.
- Enclosure: surface-mounted steel construction, rated IP20 and IK05.
- Dimensions: 460mm wide × 999mm high × 130mm deep.
- Outgoing protection: compatible GARO MCBs, RCBOs and AFDDs can be selected separately.
- Upgrade option: compatible with GARO’s optional 250A four-pole main switch upgrade kit (not included).
How Many Ways Are Available?
The GARO DTPN48 15 Way 3 Phase Distribution Board has a nominal capacity of 16 three-phase ways (48 single-phase ways). However, the factory-fitted MCB protecting the Type 2 SPD occupies one complete three-phase way.
This leaves 15 usable three-phase ways (45 single-phase module equivalents) for additional outgoing circuits. The actual circuit count depends on the number of poles and module widths of the selected MCBs, RCBOs and AFDDs.
Technical Specifications – GARO DTPN48 15 Way 3 Phase Distribution Board
| Manufacturer | GARO |
|---|---|
| Product code | DTPN48 |
| Usable three-phase outgoing ways | 15 |
| Nominal three-phase ways | 16 |
| Usable single-phase module equivalents | 45 |
| Nominal single-phase ways | 48 |
| SPD protective MCB | Factory fitted; occupies one three-phase outgoing way (3 modules) |
| Voltage range | 230–400V AC |
| Main switch | 125A four-pole, factory fitted |
| Surge protection | Type 2 SPD fitted as standard |
| Dimensions (W × H × D) | 460 × 999 × 130mm |
| Ingress protection | IP20 |
| Impact protection | IK05 |
| Busbar rating | 25kA (manufacturer stated) |
| Mounting | Surface |
| Incoming line terminal | 50mm² |
| Outgoing neutral and earth terminals | 25mm² |
| Main switch upgrade | Compatible with optional 250A four-pole main switch upgrade kit (not included) |
Selecting Outgoing Protection
The GARO DTPN48 accommodates compatible outgoing MCBs, RCBOs and AFDDs to suit the electrical installation. The protective MCB supplied with the board is dedicated to its surge protection device and cannot be used as an additional outgoing circuit.
Browse our GARO Circuit Protection Devices for suitable outgoing protective devices.
Compare Other GARO DTPN Boards
For installations requiring fewer outgoing ways, explore the other models in GARO’s three-phase distribution board range:
- GARO DTPN12 – 3 Usable Three-Phase Ways (4 Nominal)
- GARO DTPN18 – 5 Usable Three-Phase Ways (6 Nominal)
- GARO DTPN24 – 7 Usable Three-Phase Ways (8 Nominal)
- GARO DTPN36 – 11 Usable Three-Phase Ways (12 Nominal)
GARO Downloads and Related Products
Explore the GARO 3 Phase Distribution Boards category or browse our wider GARO Circuit Protection range.
Download the GARO DTPN Technical Datasheet and Declaration of Conformity or the GARO DTPN Range Brochure (October 2026) for additional manufacturer information.
Outgoing MCBs, RCBOs and AFDDs are not included unless otherwise stated. Confirm device compatibility, cable sizing and installation requirements against the manufacturer’s technical documentation.