Hager | ASZ463U | 3 Phase RCBO | 10kA | C Curve | 300mA Type A | 63A

SKU: ASZ463U
Available to Order
Estimated Lead Time:
Usually 1 - 3 Working Days
Read More

Hager ASZ463U 63A C Curve 300mA RCBO is a 10kA electronic 3P+N switched-neutral, three-module RCBO with Type A 300mA residual-current protection. C-curve response suits appropriately designed moderate-inrush circuits.

Hager ASZ463U 63A C Curve 300mA RCBO

The Hager ASZ463U 63A C Curve 300mA RCBO forms part of Hager’s electronic three-phase 10kA RCBO series. The 300mA sensitivity makes it distinct from 30mA devices commonly used where additional personal protection is required.

Understanding the 300mA Rating

This 63A / 300mA combination is for protection designs where a 300mA residual threshold is appropriate. It must not be described or relied on as the same level of additional shock protection as a 30mA RCBO. A 300mA rating is not a substitute for 30mA additional protection on circuits where that is required.

Distribution-Circuit Selection

Allow for temperature derating and the manufacturer’s installation instructions when selecting the final device. This is a C-curve product; substituting D curve changes the instantaneous-trip band and requires design verification.

Technical Specifications – Hager ASZ463U 63A C Curve 300mA RCBO

Manufacturer Hager
Part number ASZ463U
Device Electronic three-phase RCBO with switched neutral
Poles 3P+N; 3 overcurrent-protected phases
Rated current 63A
Trip characteristic C curve
Residual-current sensitivity 300mA
Residual-current class Type A
Rated breaking capacity 10kA
Module width 3 modules
Mounting DIN rail; compatible Hager Invicta distribution arrangement (verify board model)

Understanding B, C and D Trip Curves

B curve: typically 3–5 times rated current for instantaneous magnetic tripping, used for suitable low-inrush circuits. C curve: typically 5–10 times rated current, commonly specified for moderate inrush. D curve: typically 10–20 times rated current, considered for high-inrush loads such as some motors or transformers. Selected model: C curve. These bands describe magnetic tripping, not permissible continuous loading; the installed fault level and disconnection requirements must be verified.

The specific three-phase Hager range in this listing contains C- and D-curve models; no B-curve SKUs are included here.

Related Hager Three-Phase RCBOs

Compare ASZ410U (10A, 300mA) or ASX416U (C curve, 30mA) for a different rating or sensitivity.

Browse Hager Protection

Explore the Hager 3 phase RCBO range, Hager three-phase distribution boards and Hager shop.

Install and test in accordance with the Hager instructions and applicable wiring regulations. Verify the product-specific datasheet and board compatibility before ordering.