VAT:

Hager | ASY463U | 3 Phase RCBO | 10kA | C Curve | 100mA Type A | 63A

SKU: ASY463U
Available to Order
Estimated Lead Time:
Usually 1 - 3 Working Days
Read More

Hager ASY463U 63A C Curve 100mA RCBO is a 10kA electronic 3P+N switched-neutral, three-module RCBO with Type A 100mA residual-current protection. C-curve response suits appropriately designed moderate-inrush circuits.

Hager ASY463U 63A C Curve 100mA RCBO

This Hager ASY463U 63A C Curve 100mA RCBO is a three-phase C-curve RCBO rated at 100mA residual-current sensitivity. It is aimed at professionally designed circuits where the sensitivity and disconnection characteristics are appropriate.

Where 100mA Sensitivity Is Specified

The 100mA rating is not interchangeable with 30mA additional protection requirements. Allow for temperature derating and the manufacturer’s installation instructions when selecting the final device.

Current Rating and Trip Response

The 63A overcurrent setting and 100mA residual-current threshold must be checked against circuit design. 100mA residual-current sensitivity is different from the 30mA additional protection required for certain installations. This is a C-curve product; substituting D curve changes the instantaneous-trip band and requires design verification.

Technical Specifications – Hager ASY463U 63A C Curve 100mA RCBO

Manufacturer Hager
Part number ASY463U
Device Electronic three-phase RCBO with switched neutral
Poles 3P+N; 3 overcurrent-protected phases
Rated current 63A
Trip characteristic C curve
Residual-current sensitivity 100mA
Residual-current class Type A
Rated breaking capacity 10kA
Module width 3 modules
Mounting DIN rail; compatible Hager Invicta distribution arrangement (verify board model)

Understanding B, C and D Trip Curves

B curve: typically 3–5 times rated current for instantaneous magnetic tripping, used for suitable low-inrush circuits. C curve: typically 5–10 times rated current, commonly specified for moderate inrush. D curve: typically 10–20 times rated current, considered for high-inrush loads such as some motors or transformers. Selected model: C curve. These bands describe magnetic tripping, not permissible continuous loading; the installed fault level and disconnection requirements must be verified.

The specific three-phase Hager range in this listing contains C- and D-curve models; no B-curve SKUs are included here.

Related Hager Three-Phase RCBOs

Compare ASY410U (10A, 100mA) or ASZ450U (C curve, 300mA) for a different rating or sensitivity.

Browse Hager Protection

Explore the Hager 3 phase RCBO range, Hager three-phase distribution boards and Hager shop.

Install and test in accordance with the Hager instructions and applicable wiring regulations. Verify the product-specific datasheet and board compatibility before ordering.






Brand

Hager

This product will be ordered from one of ours suppliers. The usual dispatch time to you is displayed above. You will receive a notification if there are any delays once your order is placed.