VAT:

Hager | ASX420U | 3 Phase RCBO | 10kA | C Curve | 30mA Type A | 20A

SKU: ASX420U
Available to Order
Estimated Lead Time:
Usually 1 - 3 Working Days
Read More

Hager ASX420U 20A C Curve 30mA RCBO is a 10kA electronic 3P+N switched-neutral, three-module RCBO with Type A 30mA residual-current protection. C-curve response suits appropriately designed moderate-inrush circuits.

Hager ASX420U 20A C Curve 30mA RCBO

Protect a suitable three-phase circuit with the Hager ASX420U 20A C Curve 30mA RCBO, a 10kA electronic RCBO that switches the neutral as well as its three phase poles. The slim three-module format is designed for integration with compatible Hager distribution boards.

C-Curve Operation and 30mA Protection

With a 20A rating and 30mA sensitivity, this version may suit appropriate commercial three-phase final circuits. C-curve magnetic operation is typically within 5–10 × In, or approximately 100–200A at this rating. A 30mA residual-current threshold may be used for additional protection where the circuit design and regulations require it.

Planning the Installation

For motor-related loads, review starting characteristics and the protection needs of connected equipment. This is a C-curve product; substituting D curve changes the instantaneous-trip band and requires design verification.

Technical Specifications – Hager ASX420U 20A C Curve 30mA RCBO

Manufacturer Hager
Part number ASX420U
Device Electronic three-phase RCBO with switched neutral
Poles 3P+N; 3 overcurrent-protected phases
Rated current 20A
Trip characteristic C curve
Residual-current sensitivity 30mA
Residual-current class Type A
Rated breaking capacity 10kA
Module width 3 modules
Mounting DIN rail; compatible Hager Invicta distribution arrangement (verify board model)

Understanding B, C and D Trip Curves

B curve: typically 3–5 times rated current for instantaneous magnetic tripping, used for suitable low-inrush circuits. C curve: typically 5–10 times rated current, commonly specified for moderate inrush. D curve: typically 10–20 times rated current, considered for high-inrush loads such as some motors or transformers. Selected model: C curve. These bands describe magnetic tripping, not permissible continuous loading; the installed fault level and disconnection requirements must be verified.

The specific three-phase Hager range in this listing contains C- and D-curve models; no B-curve SKUs are included here.

Related Hager Three-Phase RCBOs

Compare ASX425U (25A, 30mA) or ASY416U (C curve, 100mA) for a different rating or sensitivity.

Browse Hager Protection

Explore the Hager 3 phase RCBO range, Hager three-phase distribution boards and Hager shop.

Install and test in accordance with the Hager instructions and applicable wiring regulations. Verify the product-specific datasheet and board compatibility before ordering.






Brand

Hager

This product will be ordered from one of ours suppliers. The usual dispatch time to you is displayed above. You will receive a notification if there are any delays once your order is placed.