VAT:

Niglon | MS4CBR-250TSM | 250A 4 Pole Enclosed CBR MCCB + RCD | Mild Steel

SKU: MS4CBR-250TSM
This catalogue item is offered through our quotation service.
Read More

The Niglon MS4CBR-250TSM 250A 4 Pole Enclosed CBR combines MCCB and RCD protection in an IP30 mild steel enclosure. Features adjustable 100/300/500mA earth leakage settings, selectable time delay, thermal protection and a padlockable handle. Suitable for commercial and industrial three-phase installations.

Niglon MS4CBR-250TSM 250A 4 Pole Enclosed CBR – MCCB + RCD Protection

The Niglon MS4CBR-250TSM 250A 4 Pole Enclosed CBR combines moulded case circuit breaker (MCCB) and residual current protection within a durable mild steel enclosure. Designed for commercial and industrial three-phase electrical distribution, this enclosed CBR provides protection against overloads, short circuits and earth leakage faults.

Rated at 250A for 400/415V AC applications, the unit incorporates adjustable thermal protection, selectable earth leakage sensitivity and an adjustable residual current time delay. Its IP30 steel enclosure and padlockable operating handle make it a practical solution for indoor switchgear and electrical distribution installations.

Combined MCCB and RCD Protection

The Niglon MS4CBR-250TSM integrates four-pole MCCB functionality with residual current protection, reducing the need for separate protective devices where a combined CBR meets the installation requirements.

Earth leakage protection offers three selectable residual current thresholds:

  • 100mA residual current sensitivity.
  • 300mA residual current sensitivity.
  • 500mA residual current sensitivity.

Adjustable time-delay settings of 50ms, 500ms and 800ms provide additional flexibility for coordinating earth fault protection in electrical distribution systems.

250A Four-Pole Circuit Protection

The four-pole MCCB provides overload and short-circuit protection for three-phase electrical systems. Its 250A rated current makes it suitable for higher-capacity distribution circuits, subject to the electrical installation design.

The associated 4CBR-250 device has a rated breaking capacity of 35kA at 415V and a rated ultimate short-circuit breaking capacity of 50kA at 400V AC.

Adjustable thermal protection allows the circuit breaker characteristics to be selected according to the connected load and installation requirements. Fixed magnetic protection provides automatic operation under qualifying short-circuit conditions.

Adjustable Earth Leakage and Time Delay

The Niglon MS4CBR-250TSM 250A 4 Pole Enclosed CBR supports adjustable residual current sensitivity and time delay, allowing its earth fault protection characteristics to be coordinated with other protective devices.

The appropriate settings must be determined by the electrical installation designer, taking into account the earthing arrangement, fault protection requirements and upstream or downstream device coordination.

Durable IP30 Mild Steel Enclosure

The enclosed CBR is housed in a mild steel enclosure with an epoxy powder-coated RAL7035 light grey finish, providing durable protection for the enclosed switchgear in suitable indoor environments.

The enclosure incorporates a defeatable, padlockable operating handle for convenient external operation and isolation.

The manufacturer’s enclosed CBR range catalogue lists the MS4CBR-250TSM with an enclosure measuring 500mm high x 400mm wide x 200mm deep. The fitted assembly is rated IP30.

Key Features

  • 250A rated four-pole enclosed CBR.
  • Combined MCCB and residual current protection.
  • Rated operational voltage: 400/415V AC.
  • Suitable for 50/60Hz electrical systems.
  • Adjustable thermal overload protection.
  • Fixed magnetic short-circuit protection.
  • 35kA breaking capacity at 415V for the associated CBR device.
  • Selectable 100mA, 300mA and 500mA earth leakage thresholds.
  • Adjustable 50ms, 500ms and 800ms residual current time delays.
  • IP30 mild steel enclosure.
  • RAL7035 epoxy powder-coated finish.
  • Defeatable, padlockable operating handle.
  • Designed for commercial and industrial electrical distribution.

Technical Specifications

Manufacturer Niglon
Product Code MS4CBR-250TSM
Product Type Enclosed CBR (MCCB + RCD)
Number of Poles 4 Pole
Rated Current 250A
Rated Operational Voltage 400/415V AC
Rated Frequency 50/60Hz
Rated Insulation Voltage 750V
Rated Impulse Withstand Voltage 8kV
Associated CBR Breaking Capacity 35kA at 415V
Associated CBR Ultimate Breaking Capacity 50kA at 400V AC
Thermal Protection Adjustable
Magnetic Protection Fixed
Residual Current Sensitivity 100 / 300 / 500mA
Adjustable Time Delay 50 / 500 / 800ms
Mechanical Endurance 7,000 Operations
Electrical Endurance 1,000 Operations
Enclosure Material Mild Steel
Enclosure Protection IP30
Catalogue Enclosure Dimensions 500 x 400 x 200mm
Assembly Weight 15.5kg
Finish Epoxy Powder Coated
Colour RAL7035 Light Grey
CBR Standard IEC 60947-2
Enclosure Standards IEC 61439-1, IEC 62208, IEC 60529, IEC 62262

Typical Applications

The Niglon MS4CBR-250TSM 250A 4 Pole Enclosed CBR is suitable for consideration in electrical installations requiring combined MCCB and residual current protection, including:

  • Commercial three-phase electrical distribution.
  • Industrial distribution systems and sub-main supplies.
  • Electrical plant rooms and switchgear installations.
  • Industrial machinery and fixed equipment supplies.
  • Distribution circuits requiring adjustable earth leakage protection.

Installation and Safety

Installation and commissioning must be carried out by suitably skilled electrical personnel in accordance with current UK electrical installation requirements.

Protective settings must be selected according to the electrical installation design, including prospective fault current, earthing arrangements and protection coordination.

Important: The minimum selectable residual current threshold is 100mA. This device must not be treated as providing 30mA additional protection where that level of protection is required.

Appropriate cable glands must be used to maintain the enclosure ingress protection rating. All electrical terminals should be checked for correct tightness before commissioning.






Brand